Forms and deadlines for tests

Fuel vapour recovery equipment is subject to full technical inspection and undergoes periodic and ad hoc technical tests during operation.

 

Periodic tests are carried out at the operator’s request:

 

  • once a year,
  • once every three years for automatic monitoring systems for fuel vapour recovery equipment.

 

An automatic monitoring system is a system which:

 

  • detect faults in the proper functioning of a fuel vapour recovery system and in the monitoring system itself,
  • signals that faults have been detected,
  • automatically stops the flow of petrol from a faulty liquid fuel dispenser if a fault is not rectified within 7 days.

 

Ad hoc technical tests are carried out:

 

  • at the operator’s request to obtain authorisation for placing into service after a negative result of the previous test,
  • as needed, as part of supervision over and verification of compliance with applicable laws.